For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye QS with DALI® Control Unit Quick Installation and Operation Guide
12
Zone Setup
Assigning Load Types
Load types supported by the GRAFIK
Eye QS with DALI®:
• Digital load
• DMX
• RGB/CMY DMX
• Non-dim digital
Note: For all DMX or RGB/CMY DMX lighting, an external
DMX interface (such as the QSE-CI-DMX) must be
used with the control unit.
1. Enter programming mode.
2. Use the Master buttons to
highlight “Zone setup” and press
the OK button to accept.
3. Use the Master buttons to
highlight “Load type”. Press the
OK button to accept.
4. Use the zone raise/lower buttons
to choose the load type for that
zone. See the list above for
supported load types. Press the
OK button to accept.
5. The info screen will confirm that
your load type has been saved.
6. Exit programming mode.
Assigning Non-Dim Load Type
Zones assigned to non-dim loads have five available configurations:
LOLO: Last On, Last Off
LOFO: Last On, First Off
FOFO: First On, First Off
FOLO: First On, Last Off
60/40: On at 60%, Off at 40%
Scenes made up of both dim and non-dim load types will toggle the
non-dim loads before the dim loads in a “First” on/off configuration,
and after the dim loads in a “Last” on/off configuration.
1. Enter programming mode.
2. Use the Master buttons to highlight “Zone
setup” and then press the OK button to
accept.
3. Use the Master buttons to highlight “Non-Dim
Load type”. Press the OK button to accept.
4. Use the zone raise/lower buttons to choose
the non-dim load type for that zone (zones not
programmed as non-dim will be displayed as
Unaffected). Press the OK button to accept.
5. The info screen will confirm that your load type
has been saved.
6. Exit programming mode.
Main Menu
CCI Setup
Zone Setup
Zone Setup
Load Type
Non-Dim Load Type
Saved
Load Type
Set Zones
Main Menu
CCI Setup
Zone Setup
Zone Setup
Load Type
Non-Dim Load Type
Saved
Load Type
Set Zones
12
3
4
5
6
910
11 12
13
Use the
zone
raise/lower
buttons to
choose the
load type for
that zone
OK
16