1. Make sure the wireless mode of the GRAFIK Eye QS
control unit is “Enabled”.
2. Enter programming mode.
3. Use the Master buttons to highlight “Sensor setup” and
press the OK button to accept.
4. Use the Master buttons to highlight “Add wireless
sensors” and press the OK button to accept.
5. Press and hold the “Lights Off” button (
g on some sensors) on the
occupancy sensor for 6 seconds. The lens will start flashing and the
info screen on the GRAFIK Eye QS Wireless control unit will display
the sensor’s serial number.
6. Press the OK button on the GRAFIK Eye QS control unit.
A screen will confirm that the sensor has been assigned.
To disassociate a wireless occupancy sensor from the GRAFIK Eye
QS control unit, refer to the Radio Powr Savr occupancy sensor
install guide to return the sensor to its “out-of-box” functionality.
Doing so will remove its programming from the GRAFIK Eye QS
control unit.
7. Repeat the above steps for all desired sensors.
8. Exit programming mode.
Associating Wireless Occupancy Sensors through QS Sensor
Modules (QSM)
1. Press and hold the Program button on the QSM for 3 seconds to
enter programming mode. There will be 1 audible beep and the
Status LED will begin flashing. The info screen on the GRAFIK Eye
QS control unit will display that the QSM is in programming mode.
2. Press and hold the “Lights Off” button (g on some sensors) on the
occupancy sensor for 6 seconds. There will be 3 audible beeps
from the QSM to verify association.
3. Press and hold the Program button on the QSM for 3 seconds to
exit programming mode.
Note: The wireless signal has a range of 9 m through standard
construction or 18 m line-of-sight.
Main Menu
Zone Setup
Sensor Setup
Sensor Setup
Add Wireless Sensors
Daylight
Add Wireless Sensors
Initiate Association
of Sensors
Occupancy
××××-××××
Press OK to Save
*Assigned*
OK
16
9-16
1-8
Master buttons
OK button
Timeclock (back)
button
Radio Powr Savr
Occupancy Sensors
Press and hold
“Lights Off” or g
button to associate/
disassociate
QS Sensor Module (QSM)
Program button
(continued on next page…)