EasyManua.ls Logo

Magellan MG6250 - Further Requirements; Technical Specifications

Magellan MG6250
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Version 1.6
54 | Technical Specifications
MG6250 • Section Programming Guide
Further Requirements
Certain System Timer values can be modified as long as the respect the following criteria:
[2020]-[2021] = Entry Delay maximum value is 45 seconds
[2024] = Auto-zone Shutdown value must be between 3 and 10 times
[2027] = Power Failure Report Delay maximum value is 60 minutes
[2042] = EN 50131 FTC timer maximum value is 120 seconds
[2043] = # of invalid codes before lockout value must be between 3 and 10 attempts
[2044] = Keypad lockout duration minimum value is 2 minutes
[2048] - Trouble Shutdown value must be between 3 and 10 times
[2049] - Panic Shutdown value must be between 3 and 10 times
[2111]-[2121] Bell cut-off Delay must be between 90 seconds and 15 minutes
Technical Specifications
Power input 7.5 Vdc (PA7 Power Adapter Plug)
Battery pack* 4.8V NiMH, rechargeable
Operating temperature 0°C to 50°C (32°F to 122°F)
Humidity range 5 to 90%
GPRS14 specs Quad-band GPRS/GSM module with two SIM cards
Interconnection types TIP-Ring, T1, R1, I/02, I/O1, C, -, +, battery
Current consumption Standby: 150mA, maximum: 1A
Prioritisation of signal and message
processing and indications
1. Alarm, 2. Trouble, 3. System Status
User code details All numbers for 0000 to 9999 are valid giving a total of 10 000 possible combinations
EN50131 compliancy details
For compliance to EN 50131 standards:
1) All equipment connected to the I&HAS must be of appropriate Grade
2) Programming must be as specified in the programming guide; otherwise, product marking indicating EN50131
compliance must be removed.
Life of memory support battery Memory life is not battery dependent
Dimensions (L x W x D) 21.8 x 14.7 x 3.6 cm (8.6 x 5.8 x 1.4 in.)
Weight 670 grams (1.48 lb)
EN 50131-1 & EN 50131-3 (Environmental
Class Grade 2)
EN 50131-1 & EN 50131-3 (Security Grade 2, Environmental Class II, Certification body: Intertek)
*CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT BATTERY TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.