6 Installation Startup and Autotune Guides
36 MAGNETEK HPV1000 AC Elevator Drive Technical Manual
The drive will then automatically populate the following parameters in the A1 and A5 menus:
Encoder Pulses(A1)
Rated Mtr Power (A5)
Rated Mtr Volts
Rated Motor Freq (A5)
Rated Motor Curr (A5)
Number of Poles (A5)
Motor Rated Slip (A5) - calculated from autotune
No-Load Current (A5)
Leak Inductance (A5) - calculated from autotune
Term Resistance (A5) - calculated from autotune
Low-Speed Inspection Mode
Run the drive in low-speed inspection mode and:
Start with default values for INERTIA (A1)
Verify encoder polarity. The motor phasing should match the encoder phasing. If you experience ENCODER FAULT/
HIT TRQ LIM alarm the phasing may be incorrect. This can be reversed changing ENCODER CONNECT (C1)
between C.W (clockwise) and C.C.W (counterclockwise).
Verify proper hoistway direction can be reversed with the MOTOR ROTATION and ENCODER CONNECT (C1)
parameters.