CHALLENGERSERIES10‐60KVA EXPLANATIONSOFLOGGING
AG–SD‐35Rev.No:1Rev.Date:25.09.2013PublicationNo:2 65
81 NoP.CANBusComm.
SlaveUPSwhichisoperatinginparalelmodecan’treachto
masterUPSfromCANbus.IfUPSisoperating,willbeshut
82 Ext.StartCommand
UPSwhichisoperatinginparalelmodehasbeengivena
commandtostartupbyanother(master)UPS.
83 Ext.StopCommand
UPSwhichisoperatinginparalelmodehasbeengivena
commandtostopbyanother(master)UPS.
84 Ext.SwitchToBYP.
UPSwhichisoperatinginparalelmodehasbeengivena
commandtotransfertheloadtobypassline.
85 Ext.SwitchToUPS
UPSwhichisoperatinginparalelmodehasbeengivena
commandtotransfertheloadtoinverterline.
86 ParallelComm.FE.
SlaveUPSwhichisoperatinginparalelmodehasdetecteda
failureofinputcurrentsharing.
87 InverterOKEY
InvertervoltagereachedneededvalueafterUPSisstarted
up.UPScanfeedtheloadsthroughinverter.
88 Batt.Temp.Err.
Batterytemperatureisoutofdefinedlimits,batteriescanbe
damaged.
89 BoosterOvercurrent OvercurrentinBatterymode,UPSwillbeshutdown.
90 EPOkeypressed EPOkeybuttonispressed.
91 BatteryLow
Batterycapacityhasdecreasedbelowdefined“batterylow
limit”whileUPSwasoperatinginbatterymode.
92 NoP.485BusComm.
ParallelRS485communicationbetweenthesystemsisnot
available.
93 STSOverCurrent OverCurrentinBypassline.
94 OutputSignalOFF
UPSoutputbreakeristurnedoff.Loadscannotbe
energized.
95 BYP.PhaseRot.Err.
ReversephasesequencewasdetectedinmainsattheUPS
runtime.
96 FanFailure
Unabletocommunicatewiththefancontrolsystem.Onlyfor
UPSsthatcontainthefancontrolsystem.
97 OutputDCVolt.Fault
OverInverterDCvoltage.Loadswillbetransferredtothe
bypassline.