D00619EN - v0 SWING OPERATOR - INSTALLATION MANUAL
5.14 Connector to Auxiliary Outputs
SIGNAL DEFAULT
*
DESCRIPTION FUNCTION
AUX OUT 1
AUX OUT 2
NA
A signal that, depending on its setting, can have the following configurations:
0 - Sensors supervision Signal to manage the supervised sensors.
1 - Interlocking
Allows the configuration of the device output, to enable
interlocking between the two operators.
2 - Open-door state Output that signals the open-door state.
3 - Closed-door state Output that signals the closed-door state.
4 - Malfunction Output that signals the operator malfunction state.
5 - Lock control repetition
This is a repetition of the signal that arrives from the lock
control.
AUX IN 1
AUX IN 2
NO
7 - Stand-by state
When the contact is closed, the door enters stand-by mode (unlocked
and deactivated). This logic setting only operates with the door in the
closed position.
8 - Activate again from
Stand-by
When the contact is closed, the door activates again after being in
stand-by.
9 - Step by Step function
For each impulse, the door, if closed, performs an opening manoeu-
vre, or if open, performs a closing manoeuvre.
10 - Fire alarm
VectorS: When the contact is closed, all commands are deactivated
and the door is closed by the spring
11 - Manual operation
VectorS: When the contact is closed, the door enters manual opera-
tion and the logic settings switch (Fig.1B) is excluded
12 - Door closed
VectorM: When the contact is closed, the door is placed in door-
closed mode and the logic settings switch (Fig.1B) is excluded
NO = Normally Open NC = Normally Closed
All inputs must refer to the common (COM); those indicated are preset configurations (default). These can be modified (see
section 5.17 Display Management)
NO =Normally Open NC =Normally Closed
All inputs must refer to the common (COM); those indicated are preset configurations (default). These can be modified (see
section 5.17 Display Management)
WARNING: To connect the auxiliary output signals, see the electrical connections shown in Fig. 23.
Maximum contact load: 24V - 100mA
WARNING: Overloading the card capacity may damage it.
Fig. 23.
5.14
A
LOCK
GND
DATA
PWF
RST
OUT
15VDC
COM
AUX- IN2
AUX- IN1
START 2
START 1
COM
KEY
SAFE - CLOSE
SAFE - OPEN
COM
AUX– OUT2
AUX– OUT1
A
B
A
B
+
-
-
+