SILENT 12
19
I
GB
3.2 Rotor
3.2.1 Rotor excitation field
Features:
Test method:
-Access the rotor head with the test prods
-Check that the resistance between the (+) (-)
points (Fig.9 rif.1) falls within the values indi-
cated in the table.
REMEDY: Replace the rotor
IMPORTANT
Failed output voltage may exceptionally be caused
by absence or insufficiency of residual rotor mag-
netism.
It is therefore recommended to apply for an
instant the (+) and (-) of a 12V battery on the
electronic regulator (AVR) with a 30 Ohm resis-
tor in series, respecting the polarities (+) on
terminal 3 and (-) on terminal 1
3.2 Rotore
3.2.1 Avvolgimento di campo eccitatrice
rotore
Caratteristiche:
Metodo di controllo:
-Accedere coi puntali del tester sulla testata del
rotore
-Verificare che la resistenza fra i punti (+) (-)
(Fig.9 rif.1) rientri nei valori indicati in tabella.
RIMEDIO: Sostituire il rotore
IMPORTANTE
La mancanza di tensione in uscita, può essere
causata eccezzionalmente dalla mancanza o
insufficienza di magnetismo residuo del rotore.
Si consiglia pertanto, di applicare per un istante, il
(+) e (-) di una batteria a 12V, sul regolatore
elettronico (AVR), con in serie una resistenza da
30 Ohm rispettando le polarità (+) sul morsetto 3
e (-) sul morsetto 1
3 ALTERNATOR
SILENT 12
Punti
Point
Ohm
CAMPO ECCITATRICE
EXCITATION FIELD
+ / -