11.2 ON-OFF LOGIC
Relay type
PV
Relay
LED
Hi-On
PV > SP
On
On
PV < SP
Off
Off
Open sensor
Up scale
On
On
Down scale
Off
Off
Low-On
PV > SP
Off
Off
PV < SP
On
On
Open sensor
Up scale
Off
Off
Down scale
On
On
11.3 Retransmission Output Table for OPEN /OVER /UNDER Condition
RETRASMISSION
VARIABLE
SCALE
ACTION
OPEN
OVER
UNDER
4-20mA
PV
UP
DIR
20.8
20.8
3.2
PV
DOWN
REV
3.2
3.2
20.8
PV
UP
REV
20.8
3.2
20.8
PV
DOWN
DIR
3.2
20.8
3.2
1-5V
PV
UP
DIR
5.2V
5.2V
0.8V
PV
DOWN
REV
0.8V
0.8V
5.2V
PV
UP
REV
5.2V
0.8V
5.2V
PV
DOWN
DIR
0.8V
5.2V
0.8V
NOTE: -
1. OPEN/UNDER/OVER condition is applicable to all input types except 0-5v /
0-20mA.
11.4 Linear Output Table for OPEN/OVER/ UNDER Condition
CONTROL OP
Process
Scale
Output
Direction
(O.DIR)
DISPLAY INDICATION
OPEN
OVER
UNDER
4-20mamp
UP
DIR
20.0
20.0
4.0
Current
DOWN
REV
4.0
4.0
20.0
UP
REV
20.0
4.0
20.0
DOWN
DIR
4.0
20.0
4.0
SSR
UP
DIR
ON
ON
OFF
Pulse Output