6. If required, select the required Relay Type. In most cases ML Switch works well.
Select Daisy chain only for the secondary battery in a series connection (i.e. NOT the battery to
which the relay is connected to).
Select Advanced if you are not using the ML Switch relay. In this case you also need to set the
Pulse Interval according to the manufacturer's specifications.
7. NMEA2000 Instances are used to differentiate between multiple monitoring sources.
8. To optimize the battery cycle life, the Depth of Discharge Remaining (DoD) is set to 80%.
9. Tick Show Battery Temperature to enable temperature monitoring.
10. Click OK to return to the Module Modification window and then click the Alarm/Switch Settings
button.