EasyManuals Logo
Home>McQuay>Air Handlers>RPS

McQuay RPS User Manual

McQuay RPS
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
IM-738 Page 39
Steam Coil Piping
Steam coils are provided without valves for field piping, or
piped with two-way valves and actuator motors.
The steam coil is pitched at 1/8" (3 mm) per foot (305 mm) to
provide positive condensate removal. When no factory piping
or valve is included, the coil connections are 2.5" male NPT
iron pipe.
With the factory piping and valve package, the field supply
connection is the same NPT size as the valve with female
threading (see Figure 45 on page 40).
Refer to the certified drawings for the recommended piping
entrance locations. All piping penetrations must be sealed to
prevent air and water leakage.
Note: The valve actuator spring returns to a stem up posi-
tion upon power failure. This allows full flow
through the coil.
Steam Piping Recommendations
1. Be certain that adequate piping flexibility is provided.
Stresses resulting from expansion of closely coupled pip-
ing and coil arrangement can cause serious damage.
2. Do not reduce pipe size at the coil return connection.
Carry return connection size through the dirt pocket, mak-
ing the reduction at the branch leading to the trap.
3. It is recommended that vacuum breakers be installed on
all applications to prevent retaining condensate in the coil.
Generally, the vacuum breaker is to be connected between
the coil inlet and the return main. However, if the system
has a flooded return main, the vacuum breaker should be
open to the atmosphere and the trap design should allow
venting of the large quantities of air.
4. Do not drain steam mains or takeoffs through coils. Drain
mains ahead of coils through a steam trap to the return line.
5. Do not attempt to lift condensate.
6. Pitch all supply and return steam piping down a minimum
of 1" (25 mm) per 10 feet (3 m) of direction of flow.
Steam Trap Recommendations
1. Size traps in accordance with manufacturers' recommen-
dations. Be certain that the required pressure differential
will always be available. Do not undersize.
2. Float and thermostatic or bucket traps are recommended
for low pressure steam. Use bucket traps on systems with
on-off control only.
3. Locate traps at least 12" (305 mm) below the coil return
connection.
4. Always install strainers as close as possible to the inlet
side of the trap.
5. A single tap may generally be used for coils piped in par-
allel, but an individual trap for each coil is preferred.
Steam Coil Freeze Conditions
If the air entering the steam coil is below 35°F (2°C), note the
following recommendations:
1. 5 psi (34.5 kPa) steam must be supplied to coils at all times.
2. Modulating valves are not recommended. Control should
be by means of face and bypass dampers.
3. As additional protection against freeze-up, the tap should
be installed sufficiently far below the coil to provide an
adequate hydrostatic head to ensure removal of conden-
sate during an interruption on the steam pressure. Esti-
mate 3 ft. (914 mm) for each 1 psi (7 kPa) of trap
differential required.
4. If the unit is to be operated in environments with possible
freezing temperatures, an optional freezestat is recom-
mended. See “Freeze Protection” on page 65 for addi-
tional information.
Figure 43. Hot water valve package
WARNING
Coil freeze possible. May damage equipment.
Carefully read instruction for mixing antifreeze solution
used. Some products will have higher freezing points in
their natural state than when mixed with water. The
freezing of coils is not the responsibility of McQuay
International. Refer to “Winterizing Water Coils” on
page 96.
R e t u r n
B y p a s s
S u p p l y

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay RPS and is the answer not in the manual?

McQuay RPS Specifications

General IconGeneral
BrandMcQuay
ModelRPS
CategoryAir Handlers
LanguageEnglish

Related product manuals