Fig. 6-28 Three-wire running mode 1
Where:
SB1: Stop key
SB2: FWD key
SB3: REV key
Xi is the multifunctional input terminal of X1~X6. Its corresponding terminal function shall be defined as
function No. 5 “three-wire running control”.
3: Three-wire running mode 2
Fig. 6-29 Three-wire running mode 2
Where:
SB1: Stop key
SB2: Run key
Xi is the multifunctional input terminal of X1~X6. Its corresponding terminal function shall be defined as
function No. 5 “three-wire running control”.
This function code is used to adjust the change rate of terminal UP/DOWN when setting the frequency.
The interference immunity of terminals X1~X6 can be improved by properly increasing the value of
P09.10. The longer the filtering time of the terminal is, the longer the action delay time for the terminal will
be.
K Running
direction
selection
0 FWD
1 REV
Terminal filtering time 0~500ms (10ms)P09.10
Terminal UP/DN 0.01~99.99Hz/s(1.00)P09.09