97
P13.10
Multi-stage
reference
10
Multi-stage
reference 10
0.1% 40.0% × √ ○
P13.11
Multi-stage
reference 11
Multi-stage
reference 11
0.1% 60.0% × √ ○
P13.12
Multi-stage
reference
12
Multi-stage
reference 12
0.1% 80.0% × √ ○
P13.13
Multi-stage
reference
13
Multi-stage
reference 13
0.1% 90.0% × √ ○
P13.14
Multi-stage
reference
14
Multi-stage
reference 14
0.1% 100.0% × √ ○
P13.15
Multi-stage
reference
15
Multi-stage
reference 15
0.1% 100.0% × √ ○
P13.16
Simple PLC
running
mode
selection
PLC running
mode
Unit place of LED: PLC running
mode
0: Stop after single cycle
1: Hold the end value after single
cycle
2: Continuous cycle
Tens place of LED: Start mode
0: Restart from the first section
1: Continue to run from the stage
of the stop (or fault) moment
2: Continue to run from the stage
and frequency of the stop (or
fault) moment
Hundreds place of LED: power
down storage
0: No storage
1: Save the stage and frequency
at the moment of power down
Thousands place of LED: Stage
time unit selection
0: s
1: min
1 0000 × √ ×
P13.17
Stage 1
setting
Stage 1
setting
Unit place of LED:
0: Multi-stage reference
(multi-speed or multi-stage closed
loop reference depends on
P13.00)
1: Digital reference 1: Keyboard
∧∨ reference
2: Digital reference 2: Terminal
UP/DN reference
1 000 × √ ×