Installers manual 10.03.02-R03 (201058) EN SDA-04 (SW 5.xx) - SDA-04DCB2 (SW 22.00) Page 21 of 55
Parameter 34 : (0) Behaviour of the controller after power loss
0 = After a power failure, the controller reconfigures the door in order to
determine its end points.
1 = The configuration process is stored in the controller, which will ensure that
the door will not be reconfigured upon restart after a power failure.
If parameter 34 is set to 1:
After restoration of the power while the door is in the open position, the door
will close slowly to determine the start position.
Parameter35 : (1) Limiting maximum voltage while accelerating*
Share factor to achieve maximum motor voltage
0 = Limitation disabled
1..5 = Share factor to achieve maximum motor voltage
Parameter 36 : (1) Manual override (Pull and Go)
0 = The controller does not enter into a manual override condition and
the door will not be able to be opened manually
1 = The controller enters into a manual override condition and the door can be
opened by hand and it will also travel to the partially opened position
2 = The controller enters into a manual override condition and the door can be
opened by hand and it will also travel to the fully open position
Parameter 37 : (0) Frost protection (if the motor and/or controller are in a freezer)
0 = Frost protection is disabled
1 = Frost protection is enabled, a continuous current is applied to the motor
windings to ensure that heat is generated in the motor and the controller
I. For temperatures below minus 27 °C, the motor must be insulated with
armaflex.
II. If freeze protection is enabled, input 1 must be used as an emergency
stop and input 6 connected to + with a bridge.
Parameter 38 : Reserved for future applications
Parameter39 : (0) Restoring to factory settings
0 = Standard value, no action
1 = When set to 1 all parameters will be set to their factory settings
After a reset to factory settings, the following must be reset:
Par. 30 : Motor type
Par. 31 : DIN direction (if not automatically taught-in)
Par. 33 : Closing boost
Par. 10 & 11 : (motion and power failure counters) are not reset