7.3.5 Input Configuration
Parameter 80 : (0) Toggle function (1x pulse open, 1x pulse closed)
When the door is opened all open switches operate as if they were close switches.
0 = Function disabled
1 = Function enabled
Parameter 81 : Assigned to input 1, fixed value
Parameter 82 : Assigned to input 2, fixed value
Parameter 83 : (0) Opening the door with “stop” button
(input 4) Time by which the door can be opened by means of the “stop” (input 6) button.
0 = Function disabled
1..99 = Time that the door remains open after pressing the emergency stop
Parameter 84 : Assigned to input 6, fixed value
Parameter 85 : (0) Door action in the event of a fire
(input 7)
0 = In the event of a fire alarm, the door will act as a cold smoke block; Door closes,
local control is still possible, all safety devices (photocells etc. are disabled). No
boost will be used during opening the door. (use in combination with UPS)
1 = In the event of a fire alarm, the door will act as an escape door
(The door will go to the 100% open position)
2 = In the event of a fire alarm, the door will act as a fire door
(the door will go to the closed position, all safety devices are disabled). No boost
will be used during opening the door. (use in combination with UPS)
3 = In the event of a fire alarm, the door will act as a fire door; however, if 1, the
protection devices and emergency stop will continue to work (Parameter 93 must
be set to value 3). No boost will be used during opening the door. (use in
combination with UPS)
4 = This setting works as 0, but with boost. Use in comination with heavy doors. Not
suiteable for systems which use a UPS.
5 = This setting works as 2, but with boost. Use in comination with heavy doors. Not
suiteable for systems which use a UPS.
6 = This setting works as 3, but with boost. Use in comination with heavy doors. Not
suiteable for systems which use a UPS.
Parameter 86 : (0) Function "open door" (control via a PLC)
Send open control signal to door via “latch” command (door holds the status for
as long as the contact is closed). The "one way" function will be ignored.
0 = Normal operation
1 = Input 12 activated => Fully open
2 = Input 12 activated => Fully open
Input 13 activated => Partially open