Installers manual 10.03.02-R03 (201058) EN SDA-04 (SW 5.xx) - SDA-04DCB2 (SW 22.00) Page 23 of 55
Parameter 44 : (1) “Personal Safety 4” (message PS4) only present in EN16005 mode
(input 26)
0 = Only active while closing (interrupting the signal opens the door)
1 = Only active while opening (interrupting the signal closes the door)
Parameter 45 : (5) DMS (Deceleration Measurement System)
0 = The controller will only stop the door if it detects the presence of an obstacle
1..9 = The controller will stop the door if it senses that it is slowing down or is blocked,
whereby 1 is the least sensitive and 9 is the most sensitive
Parameter 46 : (5) DMS opening/closing factor
DMS will also be activated when the door is opening. Value 0 indicates that the
DMS while opening will be 3.25 times less sensitive than while closing. When this
value is set to 9, the DMS is the same while the door is opening and closing.
0 = DMS value is 3.25 times greater while the door is closing
1..9 = The difference factor between the MDS while the door is opening and closing;
9 = the same
Parameter 47 : Reserved for future applications
Parameter 48 : Reserved for future applications
Parameter 49 : Reserved for future applications
7.3.3 Speeds
Parameter 50 : (5) Boost speed ('start')
The start speed is the speed attained when the controller delivers a lot of power.
The so-called boost speed is available momentarily in order to provide the door
with enough movement power to overcome the hermetic seal.
1..9 = Start speed 1 (threshold start speed) - 9 (220 mm/sec.)
Parameter 51 : (5) Speed during opening ('open')
Speed at which the door will open.
1..9 = 1 ( threshold speed) - 9 (maximum opening speed of 800 mm/s)
Parameter 52 : (5) Speed during closing ('close')
Speed at which the door will close.
1..9 = 1 ( threshold speed) - 9 (maximum opening speed of 400 mm/s)