Midea V5 X Series Service Manual
4.2 E0 Troubleshooting
Digital display output 4.2.1
Description 4.2.2
Communication error between outdoor units.
All units stop running.
Error code is only displayed on the slave unit with the error.
Possible causes 4.2.3
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged main PCB or electric control box communication terminals block.