V5 X VRF 50/60Hz
94 201608
Midea V5 X Series Service Manual
4.21 PL, C7 Troubleshooting
Digital display output 4.21.1
Description 4.21.2
PL indicates inverter module temperature protection. When the main inverter module temperature rises above 80
o
C,
the system displays PL protection and all units stop running.
C7 indicates PL protection has occurred 3 times in 100 minutes. When a C7 error occurs, a manual system restart is
required before the system can resume operation.
Error code is only displayed on the unit with the error.
Possible causes 4.21.3
Blocked, dirty or loose heat sink.
Temperature sensor not connected properly or has malfunctioned.
Main PCB damaged.