EasyManuals Logo

Midea MV5-X252W/V2GN1 User Manual

Midea MV5-X252W/V2GN1
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
V5 X VRF 50/60Hz
94 201608
Midea V5 X Series Service Manual
4.21 PL, C7 Troubleshooting
Digital display output 4.21.1
Description 4.21.2
PL indicates inverter module temperature protection. When the main inverter module temperature rises above 80
o
C,
the system displays PL protection and all units stop running.
C7 indicates PL protection has occurred 3 times in 100 minutes. When a C7 error occurs, a manual system restart is
required before the system can resume operation.
Error code is only displayed on the unit with the error.
Possible causes 4.21.3
Blocked, dirty or loose heat sink.
Temperature sensor not connected properly or has malfunctioned.
Main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV5-X252W/V2GN1 and is the answer not in the manual?

Midea MV5-X252W/V2GN1 Specifications

General IconGeneral
BrandMidea
ModelMV5-X252W/V2GN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals