V5 X VRF 50/60Hz
201608 63
Part 5 - Diagnosis and Troubleshooting
Procedure 4.8.4
xE9
The outdoor unit was powered on
immediately after being powered off
1
Yes
Power off the unit and wait for the digital
display to turn off before restarting the
unit
No
Replace outdoor main PCB
Notes:
1. When performing a manual restart of an outdoor unit, once the unit has been powered off it should not be powered on again until the digital display has
turned off.