V5 X VRF 50/60Hz       
72    201608 
Midea V5 X Series Service Manual 
 xL2 troubleshooting 4.11.8
Step 1: Check inverter module 
  Check the DC voltage between terminals P and N. The normal value is 510-580V, if the voltage is higher than 580V, go 
to Step 2. 
Figure 5-4.11: Inverter module terminals 
 
Step 2: Check capacitor board 
  Check the voltage between terminals P and N on the capacitor board. The normal value is 510-580V. If the voltage is 
not in the normal range, there is a problem with the electrolytic capacitor power supply. Check the power supply for 
high  or  unstable  voltage.  If  the  power  supply  voltage  value  is  normal,  then  the  main  PCB  has  malfunctioned  and 
needs to be replaced. 
Figure 5-4.12: Capacitor board terminals 
 
 xL8/xL9 troubleshooting 4.11.9
Step 1: Check compressor 
  The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W 
and ground. If any of the resistances differ from these specifications, the compressor has malfunctioned. 
  Refer to Figures 5-4.6 and 5-4.7 in Part 5, 4.11.6 “xL0 troubleshooting”. If the resistance values are normal, go to Step 
2. 
Step 2: Check compressor and main PCB 
  If there is another unit nearby (either in the same system or another system) that is operating normally, its electric 
control box can be used to determine whether the xL8/xL9 error is being caused by a compressor fault or a main PCB 
fault: 
  If using another unit in the same system as the unit with the error to perform the test, set it as the master unit 
(address 0); if using a unit in another system, use the master unit. 
  Disconnect the power wires of the compressor referenced in the xL8/xL9 error code. 
  In  the  unit  that  is  operating  normally,  disconnect  the  power  wires  that  connect  a  compressor  to  the  electric 
control box and use them to connect the compressor with the xL8/xL9 error to the electric control box of  the 
unit that is operating normally. Ensure that the U, V, W terminals are connected in the right order, and then start 
the system that is operating normally.     
  If the compressor with the xL8/xL9 error runs normally, replace the main PCB of the unit with the xL8/xL9 error