V5 X VRF 50/60Hz
88 201608
Midea V5 X Series Service Manual
4.18 xP3 Troubleshooting
Digital display output 4.18.1
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
Description 4.18.2
1P3 indicates current protection on compressor A.
2P3 indicates current protection on compressor B.
When the compressor current rises above the protection value (E705DHD-72: 23A; E655DHD-65: 21A; E405DHD-36:
12A; E405DHD-42: 15A), the system displays P3 protection and all units stop running. When the current returns to the
normal range, P3 is removed and normal operation resumes.
Error code is only displayed on the unit with the error.
Possible causes 4.18.3
Outdoor unit stop valves are closed.
Indoor load too large.
Power supply abnormal.
Sudden interruption of power to IDUs.
Excess refrigerant.
System contains air or nitrogen.
Poor condenser heat exchange.
High pressure side blockage.
Inverter module damaged.
Compressor damaged.
Main PCB damaged.
Procedure 4.18.4
xP3
ODU stop valves are closed
Yes
Open the stop valves
No
The indoor load is too large
1
Yes
Make sure the combination ratio is less
than 130%
No
The power supply is abnormal
Yes
Check the power supply equipment
No
Sudden interruption of power to IDUs
Yes
Inspect the system and fix the error
No
Flowchart continued on next page

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV5-X252W/V2GN1 and is the answer not in the manual?

Midea MV5-X252W/V2GN1 Specifications

General IconGeneral
BrandMidea
ModelMV5-X252W/V2GN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals