Series Service Manual
2.23 P4, H6: Discharge temperature protection or discharge temperature switch protection
Digital display output
Description
Discharge temperature protection.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Discharge temperature protection
Trigger condition:
For P4 protection: Discharge temperature (T7C1) ≥ 115
o
C.
Recover condition: Discharge temperature (T7C1) < 90
o
C.
Reset method:
For P4 protection: Resume automatically.
Discharge Temp. switch protection
Trigger condition: Discharge temperature ≥ 115
o
C.
Recover condition: Discharge temperature < 75
o
C.
Reset method: Resume automatically.
H6 protection
For H6 protection: P4 protection appears three times in 100 minutes.
Reset method:
For P4 protection: Resume automatically.
For H6 protection: Manually restart.
Possible causes
Outdoor unit stop valves are closed.
Temperature sensor/switch not connected
properly or has malfunction.
Insufficient refrigerant.
System blockage.
Indoor load too large.
System contains air or
nitrogen.
Poor condenser heat exchange.
Outdoor main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
Compressor TypeInverter Scroll Compressor
TypeVariable Refrigerant Flow (VRF)
RefrigerantR410A
ControlCentralized control, individual control
Indoor Unit TypesWall mounted, cassette, ducted, floor standing
Energy EfficiencyHigh energy efficiency with DC inverter technology
Indoor Unit Noise Level19 dB(A) to 45 dB(A)

Related product manuals