2.10 F3, F5, F9, FA, Fb, Fc, Fd: T6B/T6A/T5/T8/T9/TL/T7 Temperature sensor error
Digital display output
Description
F3 indicates subcooling gas temperature sensor (T6B) error.
F5 indicates injection liquid temperature sensor (T6A) error.
F9 indicates liquid pipe temperature sensor (T5) error.
FA indicates heat exchanger gas temperature sensor (T8) error.
Fb indicates heat sink temperature sensor (T9) error.
Fc indicates heat exchanger liquid temperature sensor (TL) error.
Fd indicates suction temperature sensor (T7) error.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Temperature sensor T6A/T6B/T5/T7/T8/T9/TL is open or short-circuited.
Recover condition: Temperature sensor T6A/T6B/T5/T7/T8/T9/TL connection ports can detect load.
Reset method: Resume automatically.
Possible causes
Temperature sensor not connected properly or has malfunction.
Damaged outdoor main PCB.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
Compressor TypeInverter Scroll Compressor
TypeVariable Refrigerant Flow (VRF)
RefrigerantR410A
ControlCentralized control, individual control
Indoor Unit TypesWall mounted, cassette, ducted, floor standing
Energy EfficiencyHigh energy efficiency with DC inverter technology
Indoor Unit Noise Level19 dB(A) to 45 dB(A)

Related product manuals