SPECIFICATIONS
AIRANGER XPL PLUS
Power: » 100 / 115 / 200 / 230 Vac ± 15%, 50 / 60 Hz, 31 VA
Environmental: » location : » indoor / outdoor
» altitude : » 2000 m max
» ambient temperature : » – 20 to 50 °C (– 5 to 122 °F)
» relative humidity : » suitable for outdoor (Type 4X / NEMA 4X / IP65 enclosure)
» installation category : » II
» pollution degree : » 4
Scan Points: » 10 points per AiRanger XPL Plus max
» frequency independent
Range: » 0.3 m ( 1 ft ) to 60 m ( 200 ft ) max
Accuracy: » 0.25% of program range
*
or 6 mm ( 0.24" ), whichever is greater
Resolution: » 0.1% of program range
*
or 2 mm ( 0.08" ), whichever is greater
Memory: » EEPROM ( non-volatile ) no back-up battery required
Programming: » via removable hand programmer and / or Dolphin interface package
Display: » Custom Graphics LCD
» 51 mm ( 2 in ) x 127 mm ( 5 in ) viewing area
Temperature
Compensation: » – 50 to 150 °C (– 50 to 302 °F)
» integral transducer sensor
» 1 TS-3 temperature sensor input ( expandable to 10 inputs with optional TIB-9 card ).
» programmable fixed temperature
Temperature Error: » with compensation: » 0.09% of range
» fixed temperature: » 0.17% / °C deviation from programmed temperature.
Outputs: » transducer drive: » 150 to 315 V peak ( transducer model dependent )
Communications: » proprietary bipolar current loop for Peripherals communication
(see Options) » Dolphin compatible
» SmartLinx compatible
Enclosure: » Type 4X / NEMA 4X / IP65
» 285 mm W x 209 mm H x 92 mm D ( 11.2" W x 8.2" H x 3.6" D )
» polycarbonate
Weight: » 2.3 kg ( 5 lb )
*
Program range is defined as the empty distance to the face of the
transducer (P006) plus any range extension (P801).
SPECIFICATIONS