PERIPHERALS
The XPL+ is compatible with the following Milltronics peripherals ( 3 max ).
SAM-20: 20 relay satellite alarm module ( 2 max )
AO-10: 10 output analog output module ( 1 only )
BIC-II: buffered XPL+ to RS-232C / RS-422 interface ( 1 only )
Connect the peripherals used, in a serial loop as follows:
Use Belden 8760 ( or equivalent ) 18 AWG, 2 wire shielded / twisted, 3000 m ( 10,000 ft ) total loop length.
LEVEL SYSTEM SYNCHRONIZATION
Avoid mounting the XPL+ near another ultrasonic level monitor. Likewise, when more than one monitor is
installed within a single plant / facility, ensure the transducer cables of each system are run in separate
grounded metal conduits. If this system separation is impractical, or despite separation efforts measurement
difficulties are encountered, system synchronization may be required.
To synchronize the XPL+ with an AiRanger DPL Plus or another XPL+...
1. Mount the level monitors together in one cabinet.
2. Ensure the level monitors share a common power ( mains ) supply, and ground ( earth ).
3. Interconnect the SYNC terminals of the level monitors to be synchronized.
To synchronize the XPL+ with other Milltronics ultrasonic level monitors
( not listed ) contact Milltronics or your local distributor.
INSTALLATION
PL-532 17