MASTER RESET ( P999 )
P999 MASTER RESET
A
Global Master Reset
( reset all parameters to original values ) should be performed:
» prior to initial programming if arbitrary Parameter Values were used during a "bench test".
» after replacing the XPL+ EPROM with a different software revision number.
Following a Global Master Reset, complete reprogramming is required.
A
Point Number Master Reset
( reset the non-global parameters of the displayed Point
Number to preset values ) should be performed if a Point Number is being reassigned
to a different vessel.
To perform a Global Master Reset:
1. With the Parameter Number field accessed, key in 999,
2. With the Point Number field accessed, key in 00,
3. , "C.ALL" is displayed until the reset is complete.
To perform a Point Number Master Reset:
1. With the Parameter Number field accessed, key in 999,
2. With the Point Number field accessed, key in the Point Number to
be reset ( 1 - 10 ),
3. , "C.ALL" is displayed until the reset is complete.
P999 is not accessible via SmartLinx Interace.
PL-532 82