INSTALLATION
Installation shall only be performed by qualified personnel,
and in accordance with local governing regulations.
The following procedure applies to all XPL+ level monitor installations. See
Application Examples for additional installation requirements. Also, refer to the instruction manuals of all other
equipment connected to the XPL+ for additional installation instructions.
AIRANGER XPL PLUS
Installation should only be performed by qualified personnel, and in accordance with all governing regulations.
LOCATION
Inspect all potential mounting locations. Choose a location suited to the XPL+ polycarbonate enclosure and
the following location recommendations.
The ideal XPL+ mounting location is where the:
1. Ambient temperature is always within -20 to 50 °C (-5 to 122 °F).
2. XPL+ front cover has sufficient room to swing open.
3. Operator and electronics are not exposed to the weather.
4. Cable length requirements are minimal.
5. Mounting surface is free from vibration.
Avoid mounting locations where the XPL+ is:
» exposed to direct sunlight. ( Otherwise, provide a sun shield.)
» close to high voltage or current runs, contactors, or SCR control drives.
CABLE / CONDUIT ENTRY REQUIREMENTS
Determine the number of enclosure cable / conduit entries required for:
» Transducers
» TS-3 temperature sensors ( if used )
» BIC-II ( if used )
» SAM-20 ( if used )
» AO-10 ( if used )
» Synchronization ( see Interconnection \ Level System Synchronization )
» Power
Transducer cables must be run in a grounded metal conduit, separate
from other wiring, ( except TS-3 temperature sensor wiring, if applicable ).