mA OUTPUT PARAMETERS (P200 to P203, P210 to P215, P219)
If AO-10 mA outputs are to be used, alter the following parameters as required.
Otherwise, proceed to OPERATION.
When a mA Output Parameter is accessed, the mA symbol is displayed in the Point Type field and the mA
Output Number (corresponding to the AO-10 terminals) is displayed in the Point Number field.
P200 mA RANGE
Enter the desired range of the mA output displayed.
value: 0 = OFF
1 = 0 to 20 mA
2 = 4 to 20 mA (preset)
3 = 20 to 0 mA
4 = 20 to 4 mA
P201 mA FUNCTION
Use this feature to alter the automatic mA output/measurement relationship, if desired.
The mA Function automatically corresponds to "level", "space", or "distance" based upon
Operation (P001). If a Tank Shape (P050) is programmed, the mA Function automatically
corresponds to volume (unless the mA Allocation has been altered).
values: 1 = level
2 = space
3 = distance
4 = volume
P202 mA ALLOCATION
Use this feature if Point Number to mA output allocation alteration is required.
Enter the Point Number(s) the mA output displayed, is to be based upon.
As preset, AO-10 mA outputs 1-10 are allocated to Point Numbers 1-10 respectively.
If two or more Point Numbers are allocated to a single mA output, the output value represents
the Multi Point Average. (The Quick Start Parameter values should be identical for all points).
See TECHNICAL REFERENCE/Application Examples/Example 3 - mA Multi Point Average.
When more than one mA output is allocated to the same Point Number, the mA Setpoint
parameters may be used to establish separate or overlapping mA output spans. However, the
mA Value/Transducer (P203) corresponds to the lowest mA Output number only.
values: x (x = single Point Number (1-10) to be allocated to the mA output displayed.
x.y (x = first Point Number (1-10), y = last Point Number (1-10), in the range)
20 mA = high level (unless P001 = 2 or 3, then 20 mA = low)
20 mA = low level (unless P001 = 2 or 3, then 20 mA = high)
}
}
PL-532 44