P203 (V) mA VALUE/TRANSDUCER
View the current value of the mA output associated with the Point Number displayed.
This is the Auxiliary Reading displayed when is pressed in the RUN mode and does not
include any adjustment made using the 4 or 20 mA Trim (P214, P215) features.
If the Point Number is included in a mA Multi Point Average calculation, the displayed value
is the average obtained from all Point Numbers included in the mA Allocation (P202) range.
If more than one mA output is allocated to the same Point Number, the value of the lowest mA
Output Number is displayed.
values: 0.000 to 22.00
P210 0/4 mA SETPOINT
Use this feature to reference the minimum mA output to any point in the measurement range.
Enter the material level (referenced to Empty, P006) corresponding to the minimum mA output.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation (P001).
Typically, this value is entered in Units (P005) or percent of Span (P007). If mA Function is
set for "volume", enter the value in the Max Volume (P051) units or in percent of Max Volume.
values: -999 to 9999
P211 20 mA SETPOINT
Use this feature to reference the 20 mA output to any point in the measurement range
between Empty (P006) and Span (P007).
Enter the material level (referenced to Empty, P006) corresponding to 20mA.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation (P001).
Typically, the value is entered in Units (P005) or percent of Span (P007). If mA Function is
set for "volume", enter the value in the Max Volume (P051) units or as a percent of Max Volume.
values: -999 to 9999
P212 mA MIN LIMIT
Use this feature to prevent the mA output from falling below the minimum acceptable
mA input value (preset to 3.800 mA) of the device connected.
values: 0.000 to 22.00
P213 mA MAX LIMIT
Use this feature to prevent the mA output from exceeding the maximum acceptable
mA input value (preset to 20.20 mA) of the device connected.
values: 0.000 to 22.00
APPLICATIONS PARAMETERS