SmartLinx PARAMETERS
P750 - P789 PROTOCOL SPECIFIC PARAMETERS
These parameters are specific to the SmartLinx module installed. Refer to the
module documentation for a list and description of the specific parameter requirements.
P790 HARDWARE ERROR
Use this feature to display the results of ongoing hardware tests within the communications
circuitry. If any test does not meet the PASS requirements, communication halts and tests
are repeated until PASS requirements are met. Communication then resumes.
displays: PASS: no problem
FAIL: faulty SmartLinx module or XPL+
ERR1: unknown protocol, upgrade XPL+ software
P791 BUS ERROR
This feature indicates if an error condition is occurring on the bus.
displays: 0 = no error
0 = error code, refer to the SmartLinx module documentation for
explanation of the error code
P792 BUS ERROR COUNT
This register increments by 1 each time a bus error (P752) is reported. The register is
factory set at 0 and can be preset to any value. The register is reset to 0 by master
reset (P999).
ECHO PROCESSING PARAMETERS ( P800 to P807 )
P800 NEAR BLANKING
Use this feature if the material level is incorrectly reported to be near the transducer face.
The
Near Blanking distance
( distance from the transducer face which is not ultrasonically
measurable ) is preset to a value depending on the transducer selected (P004).
blanking transducer
0.3 m (1 ft) ST-25, ST-50, ST-H, XPS-10, XPS-15
0.45 m (1.5 ft) XCT-8, XCT-12
0.6 m (2 ft) XPS-30
0.9 m (3 ft) ST-100, LR-21, XPS-40, XLS-30, XLT-30
1.2 m (4 ft) LR-13, XLS-60, XLT-60
ENHANCED PARAMETERS