TEMPERATURE COMPENSATION PARAMETERS ( P660 to P664 )
P660 TEMP SOURCE
This feature is preset to "AUTO". On scanning a transducer, the XPL+ scans the TS-3
temperature sensor
*
assigned to the transducer. If a TS-3 sensor is not connected, the
temperature measurement from the ultrasonic/temperature transducer is used. If the
transducer used does not have an integral temperature sensor, the Temp Fixed ( P661 )
value is used.
If the temperature of the atmosphere within the transducer beam varies with distance from
the transducer, connect a TS-3 temperature sensor
*
and an ultrasonic / temperature
transducer for the Point Number and select "average".
*
Unless equipped with a TIB-10 Plus Card, the XPL+ provides input terminals for only one
TS-3 connection. When a TIB-10 Plus card is installed, up to 10 TS-3 temperature sensors
may be connected. Refer to INSTALLATION TIB-10 Plus Card and Interconnection.
If the atmosphere temperature of several vessels is identical, connect a TS-3 Temperature
Sensor to terminals 21 and 22 and select "TS-3 SENSOR # 1". The temperature measurement
from the single TS-3 is used for the air temperature measurement of all Point Numbers
allocated to TS-3 number 1. ( See Temperature Sensor Allocation, P662 ).
values: 1 = AUTO
2 = Temp Fixed
3 = Ultrasonic / Temperature Transducer
4 = TS-3 Temperature Sensor
5 = Average
6 = TS-3 SENSOR # 1
P661 TEMP FIXED
Use this feature if a temperature sensing device is not used.
Enter the temperature ( in °C ) of the vessel atmosphere within the transducer beam. If the
temperature varies with distance from the transducer, enter the average temperature.
This value is preset to 20.00 °C.
values: -50 to 150