P062 OFFSET READING
Enter the value to be added to the Reading, (before display).
This feature is preset to 0.000, (no offset).
e.g. To reference a material level to sea level, enter the distance in Units (P005),
between Empty (P006) and sea level. (Enter a negative value if Empty is
below sea level.)
This feature affects the XPL+ (and BIC-II, if used) Reading only.
(Relays and mA outputs are not affected).
values: -999 to 9999
vessel
Empty
(P006)
Sea
level
display offset
(P062)
PL-532 36