RATE PARAMETERS ( P700 to P707 )
P700 MAX FILL RATE
Adjust the XPL+ response to increases in the actual material level ( or advance to a higher
Failsafe Material Level, P071 ).
Enter a value slightly greater than the maximum vessel filling rate.
This value ( in Units ( P005 ) or % of Span ( P007 ) per minute ) is automatically altered when
Measurement Response ( P003 ) is altered. See TECHNICAL REFERENCE Measurement
Response.
values: 0.000 to 9999
P701 MAX EMPTY RATE
Adjust the XPL+ response to decreases in the actual material level ( or advance to a lower
Failsafe Material Level, P071 ).
Enter a value slightly greater than the maximum vessel emptying rate.
This value ( in Units ( P005 ) or % of Span ( P007 ) per minute ) is automatically altered when
Measurement Response ( P003 ) is altered. See TECHNICAL REFERENCE Measurement
Response.
values: 0.000 to 9999
P702 FILLING INDICATOR
Enter the fill rate to activate the LCD Material Filling indicator and Smart Scan ( P720 ).
This value ( in Units ( P005 ) or % of Span ( P007 ) per minute ) is automatically set to 10%
of the Max Fill Rate ( P700 ).
values: -999 to 9999
P703 EMPTYING INDICATOR
Enter the empty rate to activate the LCD Material Emptying indicator and Smart Scan ( P720 ).
This value ( in Units ( P005 ) or % of Span ( P007 ) per minute ) is automatically set to 10%
of the Max Empty Rate ( P701 ).
values: -999 to 9999