P823 REFORM ECHO
Use this feature if the reported material level fluctuates slightly though the material
surface is still ( when monitoring solid Material ( P002 = 2 ) only ).
Enter the amount ( in ms ) of long shot Echo Profile smoothing required to eliminate
jagged peaks in the Echo Profile.
When a value is keyed in, the nearest acceptable value is entered.
values: 0 = off ( preset ), greater = wider
P825 ECHO MARKER TRIGGER
Use this feature when the reported material level fluctuates slightly, due to a variable rise in
the leading edge of the true echo on the Echo Profile.
Enter the value ( in percent of echo height ) to ensure the Echo Lock Window intersects the
Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo.
This value is preset to 50%.
values: 5 to 95
P830 TVT TYPE
Use this feature to select the TVT Curve most suited to the material and vessel.
This feature is automatically altered when Material (P002) is altered.
Do not select "TVT Slopes" when the "bF" or "bLF" Algorithm (P820) is selected.
values: 1 = TVT Short Curved
2 = TVT Short Flat
3 = TVT Long Flat
4 = TVT Long Smooth Front
5 = TVT Long Smooth
6 = TVT Slopes (see TVT Slope Min, P835)