16. Initial settings - Basic settings/operation
160
WT09991X01
16-2. Menu tab: Unit Settings
16-2-1. Sub menu tab: Groups
Register the units connected to each AE-C/EW-C.
Tapping [Unit Settings] - [Groups] will display the Group Settings screen.
Note
Group names can be up to 20 characters in length. (Recommended name length is 12 characters or less.)
However, the following characters cannot be used. < > & " '
(B-1)
(B)
(A)
(C)
(D)
Item Function and description
(A)
Target centralized
controller
Select the number of the AE-C/EW-C controller from the pull-down list.
(B) Group Name
Set the group name for each group number (B-1).
The group name set here will be displayed on the AE-C/EW-C screen.
(C) System Configuration
Register the information of the connected unit.
Select the unit type, and set the unit address.
To add a local remote controller (ME remote controller) to the system, select
its icon and set the address.
When a sub system controller exists in the system, select its icon and set the
address.
(D) [Save]/[Back]
After completing the setting, tap [Save].
To cancel the setting, tap [Back].
WT09991X01 語IB詳細(3校 正式版).book 160 ージ 2024年7月30日 火曜日 午後3時34分