16. Initial settings - Basic settings/operation
166
WT09991X01
16-2-5. Sub menu tab: Interlocked LOSSNAY
This tab is for registering the interlock settings of the LOSSNAY units for each AE-C/EW-C controller.
Tapping [Unit Settings] - [Interlocked LOSSNAY] will display the Interlocked LOSSNAY Settings screen.
(B)
(A)
(C)
(D)
Item Function and description
(A)
Target centralized
controller
Select the number of the AE-C/EW-C controller from the pull-down list.
(B) Interlocked LOSSNAY
Tap the icon displayed here, and select the address (1 to 50) of the interlocked
LOSSNAY unit.
(C) Indoor Units
Tap the icon displayed here, and select the address (1 to 50) of the indoor unit to
be interlocked.
Multiple indoor units can be selected as interlock sources.
(D) [Save]/[Back]
After completing the setting, tap [Save].
To cancel the setting, tap [Back].