13 CONTENTS AND REGISTRATION OF USER FRAMES FOR DATA COMMUNICATION
13.1 User Frame Types and Contents During Communication
257
13
C24 processing to registered code FFH+E5H
The sum check code that calculates data (message) to be transmitted/received excluding the first one frame and last one
frame is expressed as the ASCII code data and transmitted or received.
How to calculate the sum check code
Lower one byte of the calculated sum check code is converted into 2-digit ASCII code data, and transmitted and received.
Ex.
Arrangement of data when transmitted/received
C24 processing to registered code FFH+EBH
The sum check code that calculates the data (message) to be transmitted/received, including the first one frame and
excluding the last one frame, is expressed as the ASCII code data, and transmitted or received.
How to calculate the sum check code
Lower one byte of the calculated sum check code is converted into 2-digit ASCII code data, and transmitted or received.
Ex.
Arrangement of data when transmitted/received
011770 30
02H 30H
02H
03H
03H FFH+E5H
31H 31H 37H 37H 30H 33H 30H
S
T
X
E
T
X
30H+31H+31H+37H+37H+30H
=130H
User frame
(First frame)
User frame
(Last frame)
Arbitrary
data
User frame register
code
Sum
check
code
Station
No.
Read data
Transmission/
reception data code
Calculation range
011770 32
02H 30H
02H
03H
03H FFH+EBH
31H 31H 37H 37H 30H 33H 32H
S
T
X
02H+30H+31H+31H+37H+37H+30H
=132H
User frame
(First frame)
User frame
(Last frame)
Arbitrary data
User frame register
code
Sum
check
code
E
T
X
Station
No.
Read data
Transmission/
reception data code
Calculation range