40
2 DATA COMMUNICATION USING PREDEFINED PROTOCOL
2.3 Packet
Precautions
When receiving variable length data whose length exceeds the "Maximum data length", C24 stores data as long as the
maximum data length and omits the rest. (A protocol completes successfully.)
Out of packet data received from target devices, the data corresponding to variable needs to be discriminated from a
terminator or a static data immediately after non-conversion variable. The reception processing may not be performed
normally if they cannot discriminated.
Ex.
When value of a terminator or value of a static data following a non-conversion variable is used in a non-conversion variable,
C24 recognizes it as data of a terminator or a static data following a non-conversion variable and performs the verification/
reception processing.
Multiple Non-conversion variable (Fixed length) elements can be placed in a packet, and multiple Non-conversion variable
(Variable length) elements can also be placed in a send packet. However, only one Non-conversion variable (Variable length)
can be placed in a receive packet, and any of the following requirements need to be met.
Place any of the following items immediate after the non-conversion variable.
Static Data
Terminator
Check code + Static Data
Check code + Terminator
Place a Length before a Non-conversion variable and include the Non-conversion variable in the calculating range.
In addition, two or more of the following four elements cannot be placed in the same packet.
Variable number of data [Conversion variable]
Fixed number of data and variable number of digits [Conversion variable] (Excluding a case where "Number of Send Data"
is '1' and "Delimiter" is not 'No delimiter'.)
Variable length [Non-conversion variable]
Variable number of characters [Non-verified reception]