26 PARAMETER SETTING
26.2 Module Parameters
429
26
User frame specification
Set the system setting value for data communication using a user frame.
Item Description Setting range
On-demand user
frame specification
Start frame No.
designation (nth)
Sets the user frame number to be used. 0000H to 801FH
(Default: 0000H)
Final frame No.
designation (nth)
Sets the user frame number to be used. 0000H to 801FH
(Default: 0000H)
User frame
specification for
receiving
User frame use
enable/disable
designation
Sets whether or not a user frame is used for data communication. Not use
•Use
(Default: Not use)
Start frame No.
designation (nth)
Sets the user frame number to be used. 0000H to 801FH
(Default: 0000H)
Final frame No.
designation (nth)
Sets the user frame number to be used. 0000H to 801FH
(Default: 0000H)
Send user frame
designation
CR/LF output
designation
Sets whether or not CR/LF is transmitted. Do not send
Send
(Default: Do not send)
Output start pointer
designation
Sets the head position in the transmission frame number designation area to
which the registration number of the user frame to be transmitted is written.
0 to 100
(Default: 0)
Output quantity
designation
Sets the number of user frame to be transmitted from the designated position in
the output start pointer designation area.
0 to 100
(Default: 0)
Send frame number
designation (nth)
Sets the user frame number to be transmitted from the designated position in the
output start pointer designation area in the order of output.
0000H to FFFFH
(Default: 0000H)
User frame
receiving method
designation
User frame
receiving method
designation (nth)
Sets the receive format of a user frame. Method 0
Method 1
(Default: Method 0)
Method 1 dedicated
receive end data
quantity designation
(nth)
Sets the number of word/byte in the arbitrary data portion at the time of data
reception using the user frame receive method 1.
0000H to FFFFH
(Default: 0000H)