2 DATA COMMUNICATION USING PREDEFINED PROTOCOL
2.3 Packet
47
2
Non-verified reception
Use this element when received data includes unnecessary data while receiving data.
C24 skips characters as many as the specified number if a receive packet includes a non-verified reception.
Precautions
When "Data Length" is '0', the following requirements need to be met.
In received packet data from target devices, C24 needs to be able to discriminate data corresponding to a Non-verified
reception from those of a Terminator or a Static Data following a Non-verified reception. The receive processing may not be
performed normally if they cannot be distinguished.
Item Description
Element Name Set a name of the element.
Data Length 0 (variable number of
characters)
Set this item when the number of characters not to be verified varies in each of communication.
1 to 2048 (specified
number of characters)
Set the number of characters not to be verified.
Only one Non-verified reception can be placed in a packet.
Include a Non-verified reception in the calculating range of a Length. Otherwise, place any of the following data immediate after a Non-verified reception.
Static Data
Terminator
Check code + Static Data
Check code + Terminator
Two or more of the following four elements cannot be placed in the same packet.
Conversion variable (Variable number of data)
Conversion variable (Fixed number of data and Variable number of digits) (Excluding a case when the number of data is '1' with delimiter.)
Non-conversion variable (Variable length)
Non-verified reception (Variable number of characters)
Ex.) When value of a Terminator or value of a Static Data following a Non-verified reception is used in a Non-verified reception, C24 recognizes it as data
of a Terminator or a Static Data following a Non-verified reception and performs the verify/receive process.