514
APPENDICES APPENDIX
Appendix 3 Buffer Memory
9728 to 16383
(2600H to 3FFFH)
For user User setting area 2 (6656 words)
(Send/receive data monitoring function default
buffer)
Usage is determined by the user.
0RW
16384
(4000H)
16416
(4020H)
For designation
of predefined
protocol function
control data
Number of consecutive protocol executions
0: No protocol executed
1 to 8: Number of protocols to be executed
continuously
0 RW
16385
(4001H)
16417
(4021H)
Use prohibited System area
16386
(4002H)
16418
(4022H)
For designation
of predefined
protocol function
control data
Execution results
0: Normal completion
Other than 0: Abnormal completion (error code)
0 R
16387
(4003H)
16419
(4023H)
Result of the execution count
0: No protocol executed
1 to 8: Number of executed protocol for
continuous execution
0 R
16388 to
16395
(4004H to
400BH)
16420 to
16427
(4024H to
402BH)
Protocol number
0: No designation
1 to 128, 201 to 207: Protocol number to be
executed
0 RW
16396 to
16403
(400CH
to 4013H)
16428 to
16435
(402CH
to 4033H)
Matched packet No.1 to 8
0: No matched packet
1 to 16: Matched packet No.
0 R
16404 to
16415
(4014H to
401FH)
16436 to
16447
(4034H to
403FH)
Use prohibited System area
16448
(4040H)
16464
(4050H)
For designation
of predefined
protocol function
control data
Protocol cancel
0: No cancel direction (default)
1: Cancel request (set by user)
2: Cancel completed (set by C24)
0 RW
16449
(4041H)
16465
(40
51H)
For confirmation
of predefined
protocol function
execution status
Protocol execution status
0: Unexecuted (default)
1: Waiting for transmission
2: Sending
3: Waiting for data reception
4: Receiving
5: Completed
0 R Page 109 DEBUG
SUPPORT
FUNCTION
Page 473 Error Code
List
16450
(4042H)
16466
(4052H)
Predefined protocol function error code
0: Normal
Other than 0: Error (error code)
0
16451
(4043H)
16467
(4053H)
Protocol execution count
0: No log
1 to 65535: Number of executions
0
16452 to
16463
(4044H to
404FH)
16468 to
16479
(4054H to
405FH)
Use prohibited System area
16480 to 16517
(4060H to 4085H)
Use prohibited System area
Address
Dec (Hex)
Purpose Name Defaul
t value
Protocol Reference