EasyManua.ls Logo

Mitsubishi EHST20C-VM2C - Annual Maintenance Log Book; Cylinder unit maintenance record sheet; Outdoor heat pump unit maintenance record sheet; Parts which require regular replacement

Mitsubishi EHST20C-VM2C
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
105
Annual Maintenance Log Book
Contractor name Engineername
Site name Site number
Cylinder unit maintenance record sheet
Warranty number Model number
Serial number
No. Mechanical Frequency Notes
1
TurnOFFwatersupply,drainDHWtank,removemeshfromstrainer
clean and replace in strainer. *1
2
KeepwatersupplyOFF,openhotwatertapsandchecktheprimary-side
expansionvesselchargepressure.Topupifnecessary(1bar).
3
KeepwatersupplyOFFandcheckthepotablevesselchargepressure.
Top up if necessary (3.5 bar).
4
KeepwatersupplyOFF.Inhardwaterareasde-scalingoftheimmersion
heaters may be required.
5
Droptheprimary/heatingsystempressuretozerocheckandifneces-
sarytopuptheexpansionvessel(1bar).Airvalveofexpansionvesselis
TR-412.
6
TurnwatersupplyON,openthepressurereliefvalveandthentheexpan-
sionreliefvalveinturn.Checkforunrestricteddischargetothetundish
andthatthevalvesreseatcorrectly.Checktherearenoblockagesinthe
tundishandassociatedpipework.
7
Checkandifnecessarytopuptheconcentrationofanti-freeze/inhibitor(if
used in the system).
8
Topuptheprimary/heatingsystemusingatemporarybackowpreven-
tionllingloopandre-pressuriseto1bar.
9
Heatsystemandcheckpressuredoesnotriseabove3barandnowater
is released from the safety valves.
10 Release any air from the system.
11
Tocheckthe3-wayvalveforinsideleaks,conrmthatthetemperatureof
theheatemitterdoesnotrisewhenrunningtheDHWmode.
Refrigerantmodelsonly[exceptEHPT20series] Frequency Notes
1 Refer to outdoor unit manual.
Electrical Frequency Notes
1 Check condition of cables.
2 Checkratingandfusettedontheelectricitysupply.
Controller Frequency Notes
1 Checkeldsettingsagainstfactoryrecommendations.
2 Checkoperationofmotorizedvalvesensuretheyreseatcorrectly.
3 Checkbatterypowerofwirelessthermostatandreplaceifnecessary.
Outdoor heat pump unit maintenance record sheet
Model number Serial number
Mechanical Frequency Notes
1 Inspectgrillandairinletfortrappeddebris/damage.
2 Check condensate drain provision.
3 Checkintegrityofwaterpipeworkandinsulation.
4 Check all electrical connections.
5 Checkandrecordtheoperationvoltage.
* Checks should be carried out once a year.
*1Besuretoreattachthemeshafterwashing.
Note:Withintherstcoupleofmonthsofinstallation,removeandcleanthecylinderunit’sstrainermeshplusanythatarettedexternaltothecylinder
unit. This is especially important when installing on an existing system.
Inadditiontoannualservicing,itisnecessarytoreplaceorinspectsomepartsafteracertainperiodofsystemoperation.Pleaseseetablesbelowfordetailedinstruc-
tions.Replacementandinspectionofpartsshouldalwaysbedonebyacompetentpersonwithrelevanttrainingandqualications.
Parts which require regular replacement
Parts Replace every Possible failures
Pressure relief valve (PRV)
Air vent (Auto/Manual)
Drain cock (Primary/Sanitary circuit)
Manometer
Inletcontrolgroup(ICG)*
6 years Waterleakage
*
OPTIONAL PARTS for UK
Parts which require regular inspection
Parts Check every Possible failures
Immersion heater 2 years
Earthleakagecausing
circuit breaker to activate
(HeaterisalwaysOFF)
Water circulation pump 20,000 hrs (3 years)
Water circulation pump
failure
Parts which must NOT be reused when servicing
*O-ring
* Gasket
Note: Always replace the gasket for pump with a new one at each regular
maintenance (every 20,000 hours of use or every 3 years).
OCH570C

Table of Contents

Related product manuals