EasyManua.ls Logo

Mitsubishi EHST20C-VM2C - 9-4. Service Menu

Mitsubishi EHST20C-VM2C
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
Manual operation menu screen
Theservicemenuprovidesfunctionsforusebyinstallerorserviceengineer.ItisNOTintendedthehomeowneralterssettingswithinthismenu.Itisforthisreason
passwordprotectionisrequiredtopreventunauthorisedaccesstotheservicesettings.
Thefactorydefaultpasswordis"0000".
FollowtheproceduredescribedinGeneralOperationforthesetupoperation.
TheservicemenuisnavigatedusingtheF1andF2buttonstoscroll
throughthefunctions.Themenuissplitacross2screensandis
comprisedofthefollowingfunctions;
1. Manual operation
2. Functionsettings
3. Thermistoradjustment
4. Auxiliarysettings
5. Heatsourcesetting
6. Pump speed
7. Operationsettings
8. Energymonitorsettings
9. Externalinputsettings
10.Runninginformation
11.Thermistorreading
12.Summaryofsettings
13. Error history
14.Passwordprotection
15. Manual reset
16. SD card
9-4. Service Menu
Manyfunctionscannotbesetwhilsttheindoorunitisrunning.Theinstallershouldturnofftheunitbeforetryingtosetthesefunctions.Iftheinstallerattemptsto
changethesettingswhilsttheunitisrunningthemainremotecontrollerwilldisplayaremindermessagepromptingtheinstallertostopoperationbeforecontinu-
ing.Byselecting“Yes”theunitwillceaseoperation.
Selected
Running
Error
indication
<Manual operation>
Duringthellingofthesystemthewatercirculationpumpand3-wayvalvecan
bemanuallyoverriddenusingmanualoperationmode.
When manual operation is selected a small timer icon appears in the screen.
Thefunctionselectedwillonlyremaininmanualoperationforamaximumof2
hours. This is to prevent accidental permanent override of the FTC.
►Example
PressingF3buttonwillswitchmanualoperationmodeONforthemain3-way
valve.WhenllingoftheDHWtankiscompletetheinstallershouldaccessthis
menuagainandpressF3todeactivatemanualoperationofthepart.
Alternativelyafter2hoursmanualoperationmodewillnolongerbeactiveand
FTCwillresumecontrolofthepart.
Manualoperationandheatsourcesettingcannotbeselectedifthesystem
isrunning.Ascreenwillbedisplayedaskingtheinstallertostopthesystem
before these modes can be activated.
The system automatically stops 2 hours after the last operation.
<Function settings>
FunctionSettingallowsthesettingofautorecoveryafterpowerfailureandof
smartgridready.
1.FromtheservicemenuuseF1andF2tohighlightFunctionSetting.
2. Press CONFIRM.
3.EnsuretheRefaddressandunitnumberaredisplayedtotheright.
4. Press CONFIRM.
5.UseF3andF4tohighlighteither1/2/3(seebelow).
6. Press CONFIRM.
Setting Unit Mode Number
Autorecoveryafterpowerfailure Grp Mode1 1 - Inactive
2 - Active *1
3 - NO FUNCTION
Smartgridready*2
(Hotwateroperation)
1 Mode7
*3
1 - Inactive
2-Targettemp.+3°C
3-Targettemp.+5°C
Smartgridready*2
(Heatingoperation)
1 Mode8
*3
1 - Inactive
2-ThermoONtemp.+2°C
3-ThermoONtemp.+3°C
*1Approx.4-minutedelayafterpowerisrestored.
*2Referto"Smartgridready"intheindoorunitinstallationmanual.
*3Ifthemodeisnotdisplayed,FunctionSettingmustbeinitialised.EnterRequestcode“200”
in“RunningInformation”.
OCH570C

Table of Contents

Related product manuals