PARAMETERS
121
<Setting items and set data>
After completion of parameter settings, set the instruction codes and data then start
communication from the computer to allow various types of operation control and
monitoring.
No.
Item
Instruction
Code
Description
Number
of Data
Digits
Read
7B
H
0000
H
: CC-Link operation
0002
H
: Communication operation
1
Operation
mode
Write
FB
H
0000
H
: CC-Link operation
0002
H
: Communication operation
4 digits
Output frequency
[speed]
6F
H
0000
H
to FFFF
H
:Output frequency
(hexadecimal) in 0.01Hz
increments
[Speed (hexadecimal) in
r/min increments if Pr. 37 = 1
to 9998]
4 digits
Output current 70
H
0000
H
to FFFF
H
: Output current (hexadecimal)
in 0.01A increments
4 digits
Output voltage 71
H
0000
H
to FFFF
H
: Output voltage (hexadecimal)
in 0.1V increments
4 digits
0000
H
to FFFF
H
: Two most recent alarm
definitions
Alarm definition display
example (instruction code 74
H
)
Most recent alarm
(A0
H
)
b15 b8b7 b0
001100 0 0 00000011
Previous alarm
(30
H
)
Alarm data
Data
Description
Data
Description
00
H
No alarm 60
H
OLT
10
H
OC1 70
H
BE
11
H
OC2 80
H
GF
12
H
OC3 81
H
LF
20
H
OV1 90
H
OHT
21
H
OV2 A0
H
OPT
22
H
OV3 B0
H
PE
30
H
THT B1
H
PUE
31
H
THM B2
H
RET
40
H
FIN
2
Monitoring
Alarm definition
74
H
to
77
H
4 digits
3 Run command FA
H
b7
000000 01
b0
[Example 1] 02
H
…
Forward rotation
[Example 2] 00
H
…
Stop
b0:
b1: Forward rotation (STF)
b2: Reverse rotation (STR
b3:
b4:
b5:
b6:
b7:
Example 1
2 digits
4