5.2 Output setting for stoppage
5. Automatic Operation and Functions
The output value to be output just after starting the stop timer is calculated by the following formula (the
maximum value is limited to 100%).
OUT.t=A × ST.G / 100 (%)
OUT.t=Control output value just after starting the stop timer (%)
A =Control output value just before starting the stop timer (%)
ST.G =Stop gain set value (%)
5.1.3 Stop timer and Stop gain setting - - - - - - - Item number : 10
In the adjustment mode (power ON with DIP. SW8 OFF), select item number 10, and then set the stop timer
and the stop gain.
If it is not necessary to correct the inertia while stopping the machine; it is not necessary to change the initial
values.
On the adjustment / setting item selection screen, set the item number to [10],
and then press the T key.
• Setting range:
• Stop timer - - - - 0 to 30 sec - - Initial value = 0 sec
• Stop gain5 - - - - to 400% - - - - Initial value = 100%
Normally, set the stop gain to 100% or more at unwinding, and to 100% or less at winding.
5.2 Output setting for stoppage
5.2.1 Switching between manual output 1 and 2
When the [RUN] signal is OFF, the manual set value 1 will be output.
When manual output signal 2 is input, the manual set value 2 will be output.
To switch the manual output signal, select item number 50 in the adjustment mode, and then assign the
functions to the input contact terminals (MI1, MI2, or MI3).- - - - - - - - - - - - - - - - - - - - - -Refer to Sec. 6.1.2
5.2.2 Output memory function
When the [RUN] input signal is turned OFF while the output memory signal is ON, the output value sent out
just before the [RUN] input signal turning OFF will be stored in the memory. After end of the stop timer, this
memory value will be output during the [RUN] input signal is OFF.
When the output memory signal is ON, if the [RUN] input signal is repeatedly turned ON and OFF, the
output value sent out at just before final turning-OFF of the [RUN] input signal will be stored in the memory.
Turning off the power will not reset the memory value.
When the power is turned ON while the output memory signal is ON, the output value stored in the memory
is output.
When the [RUN] input signal is turned ON while the output memory signal is ON, automatic control will be
restarted using the output value stored in the memory.
When the [RUN] input signal is OFF, if the output memory signal is turned OFF, the manual set value 1 or 2
will be output.
To use the output memory signal, select item number 50 in the adjustment mode, and then assign the
function to the input contact terminal (MI1, MI2, or MI3). - - - - - - - - - - - - - - - - - - - - - - Refer to Sec. 6.1.2.