App-123
8
8
8
8
A
6
7
8
Appendix1 OPERATION PROCESSING TIME
Appendix 1.5 Operation Processing Time of LCPU
Category Instruction Condition (Device)
Processing Time (µs)
L02CPU L26CPU-BT
Min. Max. Min. Max.
Basic
instruction
LDE>=
Single
precision
In conductive status 3.900 10.000 0.0285
In non-conductive status 3.900 10.000 0.0285
ANDE>=
Single
precision
When not executed 0.120 0.0285
When
executed
In conductive status 3.400 9.300 0.0285
In non-conductive status 3.400 9.300 0.0285
ORE>=
Single
precision
When not executed 0.120 0.0285
When
executed
In conductive status 3.500 8.500 0.0285
In non-conductive status 3.500 8.500 0.0285
LDED=
Double
precision
In conductive status 4.800 16.000 3.500 9.000
In non-conductive status 4.800 16.000 3.500 9.000
ANDED=
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.400 15.100 3.200 7.500
In non-conductive status 4.400 15.100 3.200 7.500
ORED=
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.500 14.900 3.400 9.200
In non-conductive status 4.500 14.900 3.400 9.200
LDED<>
Double
precision
In conductive status 4.800 16.000 3.500 9.000
In non-conductive status 4.800 16.000 3.500 9.000
ANDED<>
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.400 15.100 3.200 7.500
In non-conductive status 4.400 15.100 3.200 7.500
ORED<>
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.500 14.900 3.400 9.200
In non-conductive status 4.500 14.900 3.400 9.200
LDED>
Double
precision
In conductive status 4.800 16.000 3.500 9.000
In non-conductive status 4.800 16.000 3.500 9.000
ANDED>
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.400 15.100 3.200 7.500
In non-conductive status 4.400 15.100 3.200 7.500
ORED>
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.500 14.900 3.400 9.200
In non-conductive status 4.500 14.900 3.400 9.200
LDED<=
Double
precision
In conductive status 4.800 16.000 3.500 9.000
In non-conductive status 4.800 16.000 3.500 9.000
ANDED<=
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.400 15.100 3.200 7.500
In non-conductive status 4.400 15.100 3.200 7.500
ORED<=
Double
precision
When not executed 0.120 0.0285
When
executed
In conductive status 4.500 14.900 3.400 9.200