12-51
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
3102
[LINK PARA. ERROR]
A CC-Link IE controller network parameter error
was detected.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
• Correct and write the network parameters.
• If the error occurs after correction, it suggests a
hardware fault. (Please consult your local
Mitsubishi representative, explaining a detailed
description of the problem.)
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*15
QnPH
*17
QnPRH
*17
QnU
[LINK PARA. ERROR]
• The network module detected a network
parameter error.
• A MELSECNET/H network parameter error was
detected.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
QCPU
[LINK PARA. ERROR]
The station No. specified in pairing setting are not
correct.
• The stations are not numbered consecutively.
• Pairing setting has not been made for the CPU
module at the normal station.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Refer to the troubleshooting of the network
module, and if the error is due to incorrect pairing
setting, reexamine the pairing setting of the
network parameter.
QnPRH
[LINK PARA. ERROR]
The CC-Link IE controller network module whose
first 5 digits of serial No. is "09041" or earlier is
mounted.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Mount the CC-Link IE controller network module
whose first 5 digits of serial No. is "09042" or later.
QnU
[LINK PARA. ERROR]
Group cyclic function in CC-Link IE controller
network that does not correspond to group cyclic
function is set.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Set group cyclic function in function version D or
later of CC-Link IE controller network.
QnU
*10
[LINK PARA. ERROR]
Paring setting in CC-Link IE controller network
modules installed in CPUs except for redundant
CPUs was performed.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Examine the paring setting for the network
parameter in the control station.
Q00J/Q00/Q01
Qn(H)
*17
QnPH
*17
QnU
*17
[LINK PARA. ERROR]
• LB/LW own station send range at LB/LW4000 or
later was set.
• LB/LW setting (2) was performed.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Correct the network range assignments of the
network parameter for the control station.
Q00J/Q00/Q01
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding