5. PARAMETERS
5 - 28
No. Symbol Name and function
Initial
value
[unit]
Setting
range
PB51 NHQ5 Notch shape selection 5
Set forms of the machine resonance suppression filter 5.
When you select "Enabled (_ _ _ 1)" of "Robust filter selection" in [Pr. PE41], the machine
resonance suppression filter 5 cannot be used.
Refer to the
"Name and
function" column.
Setting
digit
Explanation
Initial
value
_ _ _ x Machine resonance suppression filter 5 selection
0: Disabled
1: Enabled
0h
_ _ x _ Notch depth selection
0: -40 dB
1: -14 dB
2: -8 dB
3: -4 dB
0h
_ x _ _ Notch width selection
0: α = 2
1: α = 3
2: α = 4
3: α = 5
0h
x _ _ _ For manufacturer setting 0h
PB52 VRF21 Vibration suppression control 2 - Vibration frequency
Set the vibration frequency for the vibration suppression control 2 to suppress low-frequency
machine vibration.
To enable this setting, select "3 inertia mode (_ _ _ 1)" of "Vibration suppression mode
selection" in [Pr. PA24].
When "Vibration suppression control 2 tuning mode selection" is set to "Automatic setting (_ _
1 _)" in [Pr. PB02], this parameter will be set automatically. When "Manual setting (_ _ 2 _)" is
selected, the setting written to the parameter is used. The setting range of this parameter
varies, depending on the value in [Pr. PB07]. If a value out of the range is set, the vibration
suppression control will be disabled. Refer to section 7.1.5 for details.
100.0
[Hz]
0.1 to
300.0
PB53 VRF22 Vibration suppression control 2 - Resonance frequency
Set the resonance frequency for the vibration suppression control 2 to suppress low-frequency
machine vibration.
To enable this setting, select "3 inertia mode (_ _ _ 1)" of "Vibration suppression mode
selection" in [Pr. PA24].
When "Vibration suppression control 2 tuning mode selection" is set to "Automatic setting (_ _
1 _)" in [Pr. PB02], this parameter will be set automatically. When "Manual setting (_ _ 2 _)" is
selected, the setting written to the parameter is used. The setting range of this parameter
varies, depending on the value in [Pr. PB07]. If a value out of the range is set, the vibration
suppression control will be disabled. Refer to section 7.1.5 for details.
100.0
[Hz]
0.1 to
300.0
PB54 VRF23 Vibration suppression control 2 - Vibration frequency damping
Set a damping of the vibration frequency for the vibration suppression control 2 to suppress
low-frequency machine vibration.
To enable this setting, select "3 inertia mode (_ _ _ 1)" of "Vibration suppression mode
selection" in [Pr. PA24].
When "Vibration suppression control 2 tuning mode selection" is set to "Automatic setting (_ _
1 _)" in [Pr. PB02], this parameter will be set automatically. When "Manual setting (_ _ 2 _)" is
selected, the setting written to the parameter is used. Refer to section 7.1.5 for details.
0.00 0.00 to
0.30
PB55 VRF24 Vibration suppression control 2 - Resonance frequency damping
Set a damping of the resonance frequency for the vibration suppression control 2 to suppress
low-frequency machine vibration.
To enable this setting, select "3 inertia mode (_ _ _ 1)" of "Vibration suppression mode
selection" in [Pr. PA24].
When "Vibration suppression control 2 tuning mode selection" is set to "Automatic setting (_ _
1 _)" in [Pr. PB02], this parameter will be set automatically. When "Manual setting (_ _ 2 _)" is
selected, the setting written to the parameter is used. Refer to section 7.1.5 for details.
0.00 0.00 to
0.30