5. PARAMETERS
5 - 33
No. Symbol Name and function
Initial
value
[unit]
Setting
range
PC38 ERW Error excessive warning level
Set an error excessive warning level.
To enable the parameter, select "Enabled (1 _ _ _)" of "[AL. 9B Error excessive warning]
selection" in [Pr. PC05].
You can change the setting unit with "Error excessive alarm/error excessive warning level unit
selection" in [Pr. PC06].
Set the level in rev unit. Setting "0" will apply 1 rev. Setting over 200 rev will be clamped with
200 rev.
When an error reaches the set value, [AL. 9B Error excessive warning] will occur. When the
error decreases and becomes lower than the set value, the warning will be canceled
automatically. The minimum pulse width of the warning signal is 100 [ms].
Set values to satisfy the following condition: [Pr. PC38 Error excessive warning level] < [Pr.
PC01 Error excessive alarm level] [AL. 52 Error excessive] will occur first when you set as
follows: [Pr. PC38 Error excessive warning level] ≥ [Pr. PC01 Error excessive alarm level]
0
[rev]
0 to
1000
5.2.4 I/O setting parameters ([Pr. PD_ _ ])
No. Symbol Name and function
Initial
value
[unit]
Setting
range
PD02 *DIA2 Input signal automatic on selection 2 Refer to the
"Name and
function" column.
Setting digit
Explanation
Initial
value
HEX. BIN.
_ _ _ x _ _ _ x FLS (Upper stroke limit) selection
0: Disabled
1: Enabled
0h
_ _ x _ RLS (Lower stroke limit) selection
0: Disabled
1: Enabled
_ x _ _ For manufacturer setting
x _ _ _
_ _ x _ For manufacturer setting 0h
_ x _ _ 0h
x _ _ _ 0h
Convert the setting value into hexadecimal as follows.
0
BIN 0: Use for an external input signal.
BIN 1: Automatic on
Initial value
BIN HEX
Signal name
0
0
000
0
0
FLS (Upper stroke limit) selection
RLS (Lower stroke limit) selection