7. SPECIAL ADJUSTMENT FUNCTIONS 
7 -  19 
 
(b)  Switching timing chart 
After-switching gain
63.4%
CDT = 100 ms
Before-switching gain
Gain switching
Control command
from controller
OFF
ON
OFF
 
Model loop gain  100  → 50 → 100 
Load to motor inertia ratio  4.00  → 10.00 → 4.00 
Position loop gain  120  → 84 → 120 
Speed loop gain  3000  → 4000 → 3000 
Speed integral compensation  20  → 50 → 20 
Vibration suppression control 1 - Vibration 
frequency 
50  → 60 → 50 
Vibration suppression control 1 - 
Resonance frequency 
50  → 60 → 50 
Vibration suppression control 1 - Vibration 
frequency damping 
0.20  → 0.15 → 0.20 
Vibration suppression control 1 - 
Resonance frequency damping 
0.20  → 0.15 → 0.20 
Vibration suppression control 2 - Vibration 
frequency 
20  → 30 → 20 
Vibration suppression control 2 - 
Resonance frequency 
20  → 30 → 20 
Vibration suppression control 2 - Vibration 
frequency damping 
0.10  → 0.05 → 0.10 
Vibration suppression control 2 - 
Resonance frequency damping 
0.10  → 0.05 → 0.10 
 
(2)  When you choose switching by droop pulses 
The vibration suppression control after gain switching and model loop gain after gain switching cannot 
be used. 
 
(a) Setting example 
 
Parameter Symbol  Name  Setting value  Unit 
PB06  GD2  Load to motor inertia ratio  4.00  [Multiplier] 
PB08  PG2  Position loop gain  120  [rad/s] 
PB09  VG2  Speed loop gain  3000  [rad/s] 
PB10  VIC  Speed integral compensation  20  [ms] 
PB29  GD2B  Load to motor inertia ratio after 
gain switching 
10.00 [Multiplier] 
PB30  PG2B  Position loop gain after gain 
switching 
84 [rad/s] 
PB31  VG2B  Speed loop gain after gain 
switching 
4000 [rad/s] 
PB32  VICB  Speed integral compensation after 
gain switching 
50 [ms] 
PB26  CDP  Gain switching function  0003 
(switching by droop pulses) 
 
PB27  CDL  Gain switching condition  50  [pulse] 
PB28  CDT  Gain switching time constant  100  [ms]