12
TROUBLESHOOTING
12.3 Error Code List
12.3.3 Error code list (1000 to 1999)
12 - 71
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
1300
There is an output module with a blown
fuse.
Check ERR. LED of the output
modules and replace the fuse of the
module whose LED is lit.
Read the common information of the
error using the peripheral device and
replace the fuse at the output module
corresponding to the numerical value
(module No.) reading.
Alternatively, monitor special
registers SD1300 to SD1331 with the
peripheral device and change the
fuse of the output module whose bit
has a value of "1".
When a GOT is bus-connected to the
main base unit or extension base
unit, check the connection status of
the extension cable and the
grounding status of the GOT.
QnA
Q4AR
There is an output module with a
blown fuse.
External power supply for output load
is turned off or disconnected.
Check ERR. LED of the output
modules and replace the module
whose LED is lit.
Read the common information of the
error using the peripheral device and
replace the fuse at the output module
corresponding to the numerical value
(module No.) reading.
Alternatively, monitor special
registers SD1300 to SD1331 with the
peripheral device and change the
fuse of the output module whose bit
has a value of "1".
Check whether the external power
supply for output load is ON or OFF.
When a GOT is bus-connected to the
main base unit or extension base
unit, check the connection status of
the extension cable and the earth
status of the GOT.
Q2AS
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 Function version is B or later.
*5 Function version is A.
*6 The module whose first 5 digits of serial No. is 04101 or later.
*7 The module whose first 5 digits of serial No. is 07032 or later.
*8 The module whose first 5 digits of serial No. is 08032 or later.
*9 The module whose first 5 digits of serial No. is 09012 or later.
*10 The Universal model QCPU except the Q02UCPU.
*11 The Q13UDHCPU and Q26UDHCPU
*12 This applies to the QnUDE(H)CPU.
*13 The module whose first 5 digits of serial No. is 10042 or later.